Thyristor controlled reactor,TCR,TC reactor
BKKDFL 959-2X42.52/33 85MVAR SVC TCR Reactor
Ⅰ: Main technical parameters of reactor
Equipment name and model: single-phase, oil-immersed ONAF, one set of BKKDFL 959-2X42.52/33 reactor.
Rated voltage: 33kV, system voltage: 36kV
937A 186A 68A 35A 22A 15A 10A 8A 7A
Rated current:
50Hz 150Hz 250Hz 350Hz 450Hz 550Hz 650Hz 750Hz 850Hz
Rated frequency:
Cooling Type: ONAF
Rated power: 85000/3 kVA
Rated frequency: 50Hz
Number of phases: 1 ( 1/2-1/2)
Vector group: Delta with three phase
Main performance data:
Rated inductance: 2 * 42.52mH
Total loss: 112kW
Insulation level: Class A
Insulation level: LI220AC90 kV
Temperature rise:
Winding temperature rise: ≤ 65K
Oil temperature rise: ≤ 55K
Overload current: 30%
Thermal short circuit current rating ( Amps and duration time): 2.14kA 1s
Dynamic short circuit current rating (peak): 5.45kA
Ⅱ. Reactor structure and process characteristicsReactor coil material: aluminum
Reactor oil: DB25 (I-10
Current transformer: one LRB 36-2000/5, 10P20, 25VA, one LR 36-1500/5, CL.0.5, 20VA.
Tank color: RAL 7033
Ⅲ. Site conditionsAltitude: 1000 meters
Ambient temperature: 0℃~+45℃
Equipment installation method: outdoor
According to the below IEC standards:
IEC 60076-1-2011 Power Transformer,
IEC 60076-2-2011 Temperature rise for liquid-immersed transformers,
IEC 60076-3-2013 Insulation levels, dielectric tests and external clearances in air,
IEC 60076-6-2007 Reactor,
IEC 60076-7-Loading Guide 2005,
IEC 60076-8 Application Guide,
IEC 60076-10 Noise level test.